Key Features

Very low pressure losses

 Design suitable for tropical climates

R-134a Refrigerant

Operates at 60°C inlet temperature and 50°C ambient temperature

Compact design

Minimum footprint

Digital controller for energy savings

High efficiency

Ease of access

Separate electrical and cooling sections

    

What is a refrigerated air dryer? 

They cool the compressed air passing through them and keep that air dry down to the dew point of +3°C.

Inlet and outlet filters integrated into the dryer (up to the HRD 210 model) reduce the particle level by 0.01 microns and the oil particle level by 0.01 mg/m³.

TECHNICAL  SPECIFICATIONS


Model Capacity Connection Size Voltage** Refrigerant Max. Operating Pressure Maximum
Ambient
Temperature
Maximum
Inlet
Temperature
Filter Dimensions (mm) Weight
m³/min cfm bar °C °C Length Width Height kg
HRD 10 0.35 12 G ½” 230V/1/50 Hz R-134a 16 50 60 Included 423 393 567 32
HRD 20 0.58 20 G ½” 230V/1/50 Hz R-134a 16 50 60 Included 423 393 567 32
HRD 30 0.83 29 G ½” 230V/1/50 Hz R-134a 16 50 60 Included 423 393 567 32
HRD 35 1.05 37 G ½” 230V/1/50 Hz R-134a 16 50 60 Included 423 393 567 35
HRD 40 1.45 51 G ¾” 230V/1/50 Hz R-134a 16 50 60 Included 473 453 832 51
HRD 50 2.17 77 G ¾” 230V/1/50 Hz R-134a 16 50 60 Included 473 453 832 53
HRD 60 2.83 100 G ¾” 230V/1/50 Hz R-134a 16 50 60 Included 473 453 832 55
HRD 70 3.3 117 G 1 ½” 230V/1/50 Hz R-134a 16 50 60 Included 553 503 874 78
HRD 80 4.7 166 G 1 ½” 230V/1/50 Hz R-134a 16 50 60 Included 553 503 874 83
HRD 90 5.9 208 G 1 ½” 230V/1/50 Hz R-134a 16 50 60 Included 553 503 874 86
HRD 100 7.8 275 G 2” 230V/1/50 Hz R-134a 16 50 60 Included 678 648 1157 160
HRD 110 9.8 346 G 2” 230V/1/50 Hz R-134a 16 50 60 Included 678 648 1157 165
HRD 120 13.8 487 G 2” 230V/1/50 Hz R-134a 16 50 60 Included 948 728 1370 220
HRD 130 18.3 646 G 2” 230V/1/50 Hz R-134a 16 50 60 Included 948 728 1370 230
HRD 140 21.8 770 G 3” 400V/3/50Hz R-134a 16 50 60 Included 948 798 1460 270
HRD150 27.1 957 G 3” 400V/3/50Hz R-134a 16 50 60 Included 948 798 1460 285
HRD 160 36.7 1296 G 3” 400V/3/50Hz R-134a 16 50 60 Included 1163 778 1725 392
HRD 170 43.7 1543 G 3” 400V/3/50Hz R-134a 16 50 60 Included 1163 778 1725 410
HRD 180 52.4 1850 DN100 400V/3/50Hz R-134a 16 50 60 Included 1397 847 1770 492
HRD 190 61.6 2175 DN100 400V/3/50Hz R-134a 16 50 60 Included 1397 847 1770 520
HRD 200 80 2825 DN100 400V/3/50Hz R-134a 16 50 60 Included 1467 1077 1930 696
HRD 210 92 3249 DN100 400V/3/50Hz R-134a 16 50 60 Included 1467 1077 1930 718
HRD 220 109.7 3874 DN150 400V/3/50Hz R-134a 16 50 60 Not Included 2188 1062 1925 900
HRD 230 123.9 4375 DN150 400V/3/50Hz R-134a 16 50 60 Not Included 2188 1062 1925 925
HRD 240 141.6 5001 DN150 400V/3/50Hz R-134a 16 50 60 Not Included 2247 1200 2044 975
HRD 250 165.2 5834 DN200 400V/3/50Hz R-134a 16 50 60 Not Included 2247 1200 2044 1100
HRD 260 196.7 6946 DN200 400V/3/50Hz R-134a 16 50 60 Not Included 2550 1550 2100 1400
 
- Hertz Kompressoren reserves its rights to change the specifications without any prior notice.
* Capacity is given at atmospheric Pressure at 20 °C (ISO 1217) in accordance with norms ISO 7183-8573-1 and Pneurop 6611- Class 4-7 bar -35 °C inlet - 25 °C ambient.
** Consult sales representative for optional voltages